Below are details of the Main Facility at the Terminal
CATEGORY
Tanks
Description | Dimensions / Types | Capacity | Remark |
---|---|---|---|
Tank 01 | Ø=24.0m; H = 20.0m | 9,105,927 liters total capacity | Fixed Roof steel shell Tank on Pilled foundation |
Tank 02 | Ø=24.0m; H = 20.0m | 9,113,682 liters total capacity | Fixed Roof steel shell Tank on Pilled foundation |
Tank 03 | Ø=24.0m; H = 20.0m | 8,995,087 liters total capacity | Fixed Roof steel shell Tank on Pilled foundation |
Fire Water Tank 01 | Ø=15.915m; H = 15.0m | 3.0 million liters capacity | Open Roof steel shell Tank on Pilled foundation |
Slump Tank 01 | Ø=3.14m; H = 8.4m | 45,000 liters capacity | Horizontal Steel Shell Cylindrical tank |
CATEGORY
Tanks Investment System
Description | Dimensions / Types | Capacity | Remark |
---|---|---|---|
Motor Operated Valves | 12 inches | Installed at inlet to all Product Tanks | |
Motor Operated Valves | 10 inches | Installed at Outlet to all Product Tanks | |
Honey well automatic gauging system | Complete Tank Gauging system with temperature Probe | Full Operation data acquisition system installed |
CATEGORY
Product Pumps
Description | Dimensions / Types | Capacity | Remark |
---|---|---|---|
Product Pumps | Type – SNT 125 – 400 Pump; Prime Mover – SFPAM type YB2 225S-4, 37KW Electric operated Motor | Q=166 m3/h, n= 1500rpm | 4 Product pumps fully installed and ready for use |
Inter Tank Transfer /Back-loading Pump | Type – SNT 125 – 400 Pump; Prime Mover – SFPAM type YB2 250M-4, 55KW Electric operated Motor | Q=166 m3/h, n= 1500rpm | Fully install |
De-canting Pump | Type – SNT 125 – 400 Pump; Prime Mover – SFPAM type YB2 225S-4, 37KW Electric operated Motor | Q=166 m3/h, n= 1500rpm | Installed with an electronics meter (Satam) on the pump discharge line |
Spare Product Pump | Type – SNT 125 – 400 Pump; Prime Mover – SFPAM type YB2 225S-4, 37KW Electric operated Motor | Q=166 m3/h, n= 1500rpm | 1 pump deployed as spare |
Slump pump | 2inch, self priming Pump c/w 4kw, 2900rpm standard explosion proof motor | Fully installed |
CATEGORY
Gantry
Description | Dimensions / Types | Capacity | Remark |
---|---|---|---|
SATAM Metering System | Automatic Metering system | Connection with loading arms | 4 Numbers installed |
SATAM Equalis | Batch control system display unit | ||
SATAM Equalvision | Data control and batch authorization |
CATEGORY
Safety
Description | Dimensions / Types | Capacity | Remark |
---|---|---|---|
Fire Water Pump- powered by diesel | Type – NT 125 – 400 Pump; Prime Mover – DEUTZ BF 6M 1013 Diesel Engine | 400m3/h, rpm=1800 | 3 number fully installed |
Jockey Pump – electrical driven | Type – LVR10-9 Pump; Prime Mover – LEO ASYNCRNOUS MOTOR – YX3-100L- 2 | 10m3/h, rpm=2800 | 1 jockey pump installed |
HG FIRE PROTECT PVT.LTD Fixer Foam Monitor | Model – MG413 | Size 100 NB | 2 Number strategically installed to cover operation |
HG FIRE PROTECT PVT.LTD Mobil Foam unit | Model – MF-A | 160 LTR | 2 Number deployed for operation |
HG FIRE PROTECT PVT.LTD Bladder Tank | Foam Proportioning System | 3500 liter | 1 Fully installed |
Oil Water Separator | Concrete structure with Oil skimming pipe system installed | 25,000 liters | Grating cover on pit top |
CATEGORY
Power
Description | Dimensions / Types | Capacity | Remark |
---|---|---|---|
Generator Set 01 | JUBAILI BROS JP500 | 500KVA | Fully installed |
Generator Set 02 | Marapco MP300 | 300KVA | Fully installed |
Generator Set 03 | Marapco MP60 | 60KVA | Fully installed |
CATEGORY
Others
Description | Dimensions / Types | Capacity | Remark |
---|---|---|---|
Cargo line | Ø10 inch and 12 inch schedule 40 steel pipe line in-one | 10 inch = 216m and 12 inch = 180m | Installed |
Primary Bund Wall | Reinforced concrete walls | Tank Area fully bonded | Completed |
Secondary Bund Wall | Earthen bund wall | 3 Product’s Tanks bonded on the secondary side | Completed |